Sweep Frequency Response Analyzer for Transformer Winding Deformation Test

Product Details
Customization: Available
Type: Strength Testing Machine
Accuracy Grade: 0.1dB
Shipping & Policy
Shipping Cost: Contact the supplier about freight and estimated delivery time.
Payment Methods:
visa mastercard discover JCB diners club american express T/T
PIX SPEI OXXO PSE OZOW
  Support payments in USD
Secure payments: Every payment you make on Made-in-China.com is protected by the platform.
Refund policy: Claim a refund if your order doesn't ship, is missing, or arrives with product issues.

360° Virtual Tour

Secured Trading Service
Diamond Member Since 2018

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
30000000 RMB
Plant Area
10000 square meters
  • Sweep Frequency Response Analyzer for Transformer Winding Deformation Test
  • Sweep Frequency Response Analyzer for Transformer Winding Deformation Test
  • Sweep Frequency Response Analyzer for Transformer Winding Deformation Test
  • Sweep Frequency Response Analyzer for Transformer Winding Deformation Test
Find Similar Products

Basic Info.

Model NO.
HM5010
Weight
4kg
Test Range
(-100dB) - (+20dB)
Frequency Accuracy
<0.01%
Transport Package
Wooden Box with Foam Inside
Specification
31cm *15cm *15cm
Trademark
GDHM
Origin
Hubei, China(Mainland)
HS Code
9030899090
Production Capacity
500 Set Per Year

Product Description

PRODUCT DESCRIPTION

Sweep Frequency Response Analyzer based on the measurement of the windings characteristic parameters inside the transformer, the tester using the world's developed countries sound internal fault frequency response analysis (FRA) method, able to make an accurate internal transformer fault judgment.
After the completion of the design and manufacture transformers, coils and its internal structure to be finalized, therefore a transformer coil winding, if the voltage level, method of winding are the same, each coil corresponding parameters (Ci, Li) is determined. Thus the frequency domain response characteristics of each coil also will determine, among the corresponding three-phase coil has a comparable frequency spectrum.  
It occurs inter-turn, phase short circuit during the test or collision during transport, causing the coil relative displacement, and during operation under short circuit and fault conditions due to the tension caused by the electromagnetic, coil is deformed, it will make the distribution parameters of the transformer windings changes. Thus influent and change the existing frequency domain transformer frequency response feature, that frequency response amplitude changes occur and resonance frequency shift, etc. HTBX-H applies to the internal structure of fault detection 63kV ~ 500kV power transformers.
FRA quantization process transformer internal winding parameters response changes in the different frequency domain, according to thevalue of the change magnitude, frequency response magnitude change, regional and response trends, to judge the transformer internal windings degree of change, in turn, can determine whether the transformer has been severely damaged, need to overhaul measurement.
For the running transformer, regardless of whether there is a saved frequency domain feature picture in the past, by comparison the difference between fingerprints of fault transformer coil can also judge the degree of fault. Of course, if you save a set of transformer windings original characteristic graph easier for the operation of transformers, maintenance and inspection after the accident analysis and provide a strong basis more accurate.
FRA from the laptop and chip microprocessor precision measurement systems, compact, easy to operate, with comprehensive test analysis function.



Sweep Frequency Response Analyzer for Transformer Winding Deformation Test

characteristics
1.Transformer winding deformation tester consists of measurement part and analysis software part. The measurement part is high speed single chip microcomputer control, which is composed of signal generation and signal measurement. The measurement part is connected with the tablet computer by the wireless Bluetooth interface, without wiring, easy to use, and can also be connected with a tablet computer or a notebook computer by using the USB interface.

2.In the test process, only need to remove the transformer connection bus, without the transformer hanging cover, disassembly and completion of all tests.
 
3.Instruments have a variety of linear sweep frequency measurement frequency measurement system, linear sweep frequency measurement of scanning frequency up to 10MHz, frequency scanning interval can be divided into 0.25kHz, 0.5kHz and 1kHz, to provide more analysis of deformation of transformer.

4.Intelligent instrument, easy to use, automatic range adjustment, automatic sampling, frequency regulation and other functions.
 
5.Software adopts windows platform and is compatible with windows98/2000/winXP/Windows7 system. A more convenient and easy to use display interface is provided for users.
 
6.Provide historical curve contrast analysis, may simultaneously load several historical curves to observe, can select any curve to carry on the crosswise and the longitudinal analysis specifically. With the analysis of expert intelligent diagnosis system, which can automatically diagnose the transformer winding, while loading the 6 curves, automatically calculate the related parameters of each curve, automatic winding deformation diagnosis, diagnostic reference conclusions are given.
 
7.Software management is powerful, fully considering the needs of field use, automatic preservation of environmental parameters, in order to provide the basis for transformer winding deformation diagnosis. The measurement data is automatically saved and has the function of color printing, which is convenient for users to give out test reports.
 
8.Humanization software features, conditions of measuring more options, with transformer parameters can be stored for diagnosis, and not at the scene can later add input, modify the information, more convenient to use.
 
9.Software is a high degree of intelligence, after connected in the input and output signals, set the parameters, you can complete all of the measurements, and can open the historical wave curves are compared with observation and measurement in the measurement stop.
 
10.Each phase measuring time is less than 60 seconds, for a high, medium and low winding power transformer (capacity, voltage level is not limited) for winding deformation measurement, the total time does not exceed 10 minutes.
 
11.When measuring the transformer, the wiring staff can arbitrarily output the signal input and output lead, and have no influence on the measurement result. The wiring personnel can stay on the transformer oil tank, and do not need to come down to reduce the labor intensity.

Technical data
1,Two different sweep modes: Linear sweep,Section sweep;
    Linear sweep:
    0.5KHZ-1MHZ interval 0.5KHZ 2000 dots
    Section sweep:
    50HZ-100HZ interval 2HZ 25 dots
    100HZ-1KHZ interval 20HZ 45 dots
    1KHZ -10KHZ interval 50HZ 180 dots
    10KHZ-100KHZ interval 0.2KHZ 450 dots  
    100KHZ - 500KHZ interval 0.5KHZ 800 dots
    500KHZ - 1000KHZ interval 1KHZ 500 dots
2, Test range:(-100dB) - (+20dB)
3, Test accuracy:0.1dB;
4, Frequency accuracy:<0.01%;
5, Signal input impedance:>1M Ω;
6, Signal output impedance:50 Ω;

Sweep Frequency Response Analyzer for Transformer Winding Deformation Test
Sweep Frequency Response Analyzer for Transformer Winding Deformation Test
Sweep Frequency Response Analyzer for Transformer Winding Deformation Test

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier