| Customization: | Available |
|---|---|
| After-sales Service: | Life Long Support |
| Warranty: | 1 Year |
| Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
|---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency


Products name | Cable Fault Location Vehicle |
Products model | HM-A40 |
Display | 15-inch industrial LCD (Linux operating system) |
resolution | 1024×768 |
Storage | 32GB electronic disk |
Test methods | low-voltage pulse, high-voltage flashover, multiple pulse, DC / burn-through. |
Burn-through mode | output voltage 0–40 kV; output current 0–100 mA. |
Operation mode | photoelectric rotary knob (touchscreen optional) |
Pulse width / pulse amplitude | 100 ns – 10 μs, 120 V |
Gain adjustment | -20 to +40 dB. |
Output impedance matching | 120 Ω |
Test range | 5m ~ 100km |
Minimum test distance (blind zone) | 5m |
Pinpointing accuracy | ±0.2 m |
Test error | less than ±1%. |
Multiple pulse generator | impulse voltage ≤ 40 kV. |
Resolution | (v/2) × f meters (v/2: half-wave velocity in m/μs; f: sampling frequency in MHz). |
Sampling frequencies | 200MHz,100MHz,50MHz,25MHz,12.5MHz,6.25MHz |
Positioning accuracy | ±(0.2% · L + 1) m. |