Portable cable test and fault location system on low and medium voltage power cables
Product features
HM-A300 is used for main insulation fault pre-locating, It can test various faults of power cables of different voltage levels, different cross sections, different media and various materials under 35KV, including: open circuit, short circuit, low resistance, high resistance leakage, high resistance flashover fault etc. And accurate testing of railway airport signal control cables and streetlight cable faults. Working method: TDR,ICE,ARC
Componet's information:
Application:
I. Power cable fault pre-locator
- It is used for main insulation fault pre-locating, It can test various faults of power cables of different voltage levels, different cross sections, different media and various materials under 35KV, including: open circuit, short circuit, low resistance, high resistance leakage, high resistance flashover fault etc. And accurate testing of railway airport signal control cables and streetlight cable faults.
- Working method: TDR,ICE,ARC
Main Technical parameter
1.It can test various faults of power cables of different voltage levels, different cross sections, different media and various materials under 35KV, including: open circuit, short circuit, low resistance, high resistance leakage, high resistance flashover fault etc.
2.It can test various faults of railway communication control cable, street light cable, airport signal cable,
3.Measure the speed of radio wave propagation in any cable of known length.
4.Testable power cable buried path and buried depth
5.It shall be capable of locating /detecting all underground transmission cable fault up to 35 KV network
6.Display method: 12.1-inch industrial grade LCD screen (win7 operating platform)
6.Testing distance≤100km.
7.Operation method: Dual operation, touch pen and touch mouse operation
8.Testing method: Low-voltage pulse method, flash current method, multiple pulse method.
9.Storage: 8G
10.Shortest test distance (blind area):0-5m or no blind area
11.Resolution: V/fm; V is the wave velocity m/μs; software cursor 0.10 m
12.Accuracy Pointed error: ±0.2m
Testing error: system error ≤±1%
13.Instrument sampling frequency:3.125 MHz ,6.25MHz,12.5MHz,25MHz,50MHz,100MHz,200 MHz,250 MHz;
14.Pulse Width: 50ns,80 ns,100ns,200 ns,1μs,2μs,5μs,10μs (automatic match)
15.Standby time: Can be used continuously for about 6 hours
16.Host net weight: 8kg
17.Host measuring size: 180mm×300mm×400mm
18. Environment temperature :-20ºC~+40ºC,relative humidity:80%
19. Power and power consumption:AC 220V±10% ≤15W DC 12V(7AH) ≤ 20W
II.Power cable fault location multiple impluse generator
Application:
- Used to offer the multi-impluse coupling signal for the cable fault location
- Automatically analyse the fault waveform cooperated with HM-300 Host
Main parameter
- Output voltage <40kV
- Power supply: AC 220V, 50hZ.
III. Cable fault locating HV signal generator
Application:
Inject the impluse high voltage into the faulty cable to repeat the fault for pre-locating and pinpointing
Main Technical Parameter
1.Output voltage:Negative pressure, 0~-35kv continuously adjustable
2.Working current:≤40mA
3.Operating mode: Single pulse, continuous pulse, DC output
4.Built-in capacitor:2uF/35kv
5.Discharge energy:≤1225J
6.Pulse period:3s~8s automatic
7.Automatic discharge: Automatic discharge at shutdown
8.Working power:220V±10%
9.Operating temperature:-10ºC~40ºC
10.Working humidity:≤80% Altitude:≤1000m
IV.Cable Fault Tracing and Pinpointer
Application:
Power cable main insulation path tracing and fault p
Inpointing.
HM-R10 path meter
- Detection distance< 15km
- Detection depth ≤ 3m
- Routing error< 5cm
- Transmitter
Output frequency:9.82kHz
output power:2W
- Routing receiver:
Input frequency:9.82kHz
Detection routing error:±2cm
Detection of buried depth error:±5cm
Battery: 9V laminated battery, working 8 hours continuously
- HM-C10A cable fault sound magnetic precision point meter
- 1.Sensor dynamic range:Sound channel>104dB.
2.Shock discharge sound amplification>90dB,Shock discharge volume upper 3.limit84dB(A)
4.LCD Monitor: Highlight true color screen 320 x 240,adopt to outdoor.
5. On-site continuous working hours:Alkaline replaceable battery for easy on-site use
V.Appilication: