Gas Chromatography Dga Dielectric Insulating Transformer Oil Dissolved Gas Analyzer
| Customization: | Available |
|---|---|
| Customized: | Customized |
| Structure: | Portable |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ISO9001:2015 certificate
ISO45001:2018 certificate
ISO14001
CE
Find Similar Products
Basic Info.
- Model NO.
- hm9890
- Material
- Steel
- Certification
- ISO
- Application
- Lab
- Type
- Measurement Type
- Baseline Noise
- ≤2 *10-13A
- Linear
- >106
- Sensitivity
- >5000mv Ml / Mg
- Baseline Drift
- ≤100μV / 30min
- Product Name
- Transformer Oil Dissolved Gas Analyzer
- Transport Package
- Wooden Box with Foam Inside
- Trademark
- HMDQ
- Origin
- Hubei, China(Mainland)
- Production Capacity
- 100sets Per Year
Product Description
I. Application
Suitable for the determination of the content of dissolved gas components in insulating oil of electric power system. It can complete 7 kinds of gas components H2, CO, CO2, CH4, C2H4, C2H6, C2H2 (hydrogen, carbon monoxide, carbon dioxide) dissolved in insulating oil at one injection. Full analysis of the content of methane, ethylene, ethane, acetylene, and the minimum detectable concentration of acetylene was 0.06 ppm.
II.Specification :
The detection limit: ≤2 × 10-12g / s (n-hexadecane / iso-octane)
Baseline Noise: ≤2 × 10-13A
Baseline Drift: ≤2 × 10-12A / 30min
Linear: ≥106
Adjustable automatic ignition
Settling time: ten minutes
the thermal conductivity detector (TCD):
Semi-diffused structure
Power supply with constant current control mode
Sensitivity: ≥5000mV · ml / mg.
Baseline noise: ≤10μV.
Baseline Drift: ≤100μV / 30min.
Linear ≥ 105
large-screen LCD display:
Clearly show the temperature set point and the brightest, the measured
values and the protection value
Real-time status display instrument
Automatic ignition
temperature indicators:
Oven: the temperature 5 °C ~ 420 °C Accuracy ± 0.05 °C
Injector: The room temperature 5 °C ~ 420 °C Accuracy ± 0.05 °C
Detector: the temperature 5 °C ~ 420 °C Accuracy ± 0.05 °C
Reformer: The room temperature 5 °C ~ 420 °C Accuracy ± 0.05 °C
the other parameters:
Power: 220V ± 22V, 50Hz,
Power: ≥2 kW