Transformer Capacitance & Dissipation Factor Tan Delta tester
I. Summary
Tan Delta Test Set is a basic method in insulation test and effectively detect damp, degradation and partial defect of insulation of electrical equipment. This method is widely used in electric manufacturing, electric equipment installation, connection and preventive test. Measurement on dielectric loss of transformer, mutual inductor, reactor, capacitor, bushing and arrester is the most basic method to test their insulation property. It features strong anti-interference capacity, high test speed, high precision, automatic digitization and easy operation.
II. Technical indicators Accuracy: Cx: ±(reading×1%+1pF) tgδ: ±(reading×1%+0.00040)
Anti-interference: Variable frequency anti-interference, the above accuracy can be reached under 200% interference.
Capacitance range: Internal HV: 3pF~60000pF/10kV 60pF~1μF/0.5kV External HV: 3pF~1.5μF/10kV60pF~30μF/0.5kV Resolution: Maximum 0.001pF, 4 valid figures.
tgδ range:unlimited, 0.001% resolution,automatic identification for capacitance, inductance and resistance of three tested articles.
Test current range: 10μA~1A
Internal HV: Set voltage range: 0.5~10kV Maximum output current: 200mA
Buck-bust method: continuous stepless regulation Test frequency: 45, 50, 55 single frequency 45/55Hz automatic dual variable frequency
Frequency accuracy: ±0.01Hz
External HV: In case of UST, maximum test current is 1A,andpower frequency or variable frequency is 40-70Hz In case of GST, maximum test current is 10kV/1A, and power frequency or variable frequency is 40-70Hz CVT self-exciting low voltage output: Output voltage 3~50V, output current 3~30A