High Voltage Circuit Breaker Analyzer Instrument Price

Product Details
Customization: Available
Humidity: <=80%Rh
Temperature: 10~40ºC
Shipping & Policy
Shipping Cost: Contact the supplier about freight and estimated delivery time.
Payment Methods:
visa mastercard discover JCB diners club american express T/T
PIX SPEI OXXO PSE OZOW
  Support payments in USD
Secure payments: Every payment you make on Made-in-China.com is protected by the platform.
Refund policy: Claim a refund if your order doesn't ship, is missing, or arrives with product issues.

360° Virtual Tour

Secured Trading Service
Diamond Member Since 2018

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
30000000 RMB
Plant Area
10000 square meters
  • High Voltage Circuit Breaker Analyzer Instrument Price
  • High Voltage Circuit Breaker Analyzer Instrument Price
  • High Voltage Circuit Breaker Analyzer Instrument Price
  • High Voltage Circuit Breaker Analyzer Instrument Price
  • High Voltage Circuit Breaker Analyzer Instrument Price
Find Similar Products

Basic Info.

Model NO.
HM6081
Current
Range: 20.00A, Resolution: 0.01A
Output Power
DC30~250V Digitally Adjustable /20A (Instantaneous
Transport Package
Wooden Box with Foam Inside
Specification
360mm (L) *280mm (W) *300mm (H)
Trademark
GDHM
Origin
Hubei, China(Mainland)
HS Code
9031809090
Production Capacity
500sets/Month Circuit Breaker Test Kit

Product Description

High Voltage Circuit Breaker Analyzer  instrument Price
  1. Brief introduction
It is suitable for mechanical characteristic testing for all types of SF6 switch, GIS switchgear, vacuum switch and oil switch with metal contact manufactured at home and abroad.

Hot tags : circuit breaker analyzer, Circuit breaker Tester, Circuit Breaker Test Equipment

 
  1. Main features
  1. With excellent robustness, the test result is accurately even in 500kV power substation .
  2. With universal speed sensor, linear travel sensor and rotation sensor, very convenient and easy to install it .
  3. With laser sensor, test in high accuracy .
  4. Possible to get all data and graph of swithgear mechanical characteristic once it act one time .
  5. Built in function of 600A contact resistance testing , tested result can be printed out directly .
  6. Available to store 1000 groups data , real time color ensure store the date and time for each testing .
  7. Available to transfer data by USB stick .
  8. Large liquid crystal screen, with background light.
  9. Built-in micro computer ,
  10. With RS-232 interface, can be operated by computer directly , and all test data stored into computer .
 
  1. Performance
  1. Time: intrinsic switch off time and switch on time, in-phase synchronization and phase to phase synchronization of 12 breaks.
 
  1. Closing resistance: Pre cast time,Pre cast waveform and resistance of closing resistance of six breaks. (DB-8001(II) has closing resistance)
 
  1. Re-close: time of switch on-switch off, switch off-switch on, switch off-switch on-switch off .
 
  1. Bounce: switch on bouncing time, bouncing times, bouncing process and bouncing waveform of each break; switch off rebound amplitude of each break.
 
  1. Speed: instantaneous opening speed and instantaneous closing speed, maximum speed, time-travel characteristic curve
 
  1. Travel: total travel, opening, over-travel, overshoot travel, rebound amplitude.   
Current: Switch off current and switch on current of switch off and switch on coils, current oscillogram.  
 
  1. Operating pressure: DC30~250V/20A of digital regulated operating power supply of circuit breaker is supplied in the device, and test of low-pressure operating is completed automatically to measure the operating voltage of circuit breaker


IV. Technical Specification
1. Time:
Normal switchgear: Measurement range 5.0ms~16s   Resolution:0.1ms
Error      1.  within 100ms  0.1ms±1 digits
                2.above 100ms   0.1%±1 digits
               3.Synchronization  ±0.1ms  
Closing resistance: Measurement range  20000Ω    Resolution:1 Ω
Graphite contact:  Measurement range 5.0ms~16s   Resolution:0. 1m/s
           Error  0.5%±1 digits
                  Synchronization±0.1ms
  1. Speed: Measurement range: 20.00m/s       Resolution: 0.01m/s
               Error 1%±0.1m/s
  1. Measurement range
  Measurement range Resolution Error
Vacuum circuit breaker 50.0mm 0.1mm
1%±1mm
SF6 Circuit breaker 300.0mm 1mm
Oil-minimum breaker 600.0mm


4.Current:Measurement range  20.00A              Resolution : 0.01A
5. Output power: DC30~250V digital adjustable /20A(instantaneous working)
6. Computer interfacestandard RS-232 interface , U disk interface

High Voltage Circuit Breaker Analyzer Instrument Price








High Voltage Circuit Breaker Analyzer Instrument Price